Plans are required prior to the issuance of any kind of permit.

AUTOMATIC FIRE SPRINKLER PLAN SUBMITTALS REQUIREMENTS:
  1. Plan size shall be no smaller than 24”x36
  2. Scale shall be no smaller than 1/8”= 1 foot
  3. A minimum of three (3) sets of plans is required
  4. A minimum of two (2) sets of hydraulic calculations is required
  5. Proof calculations may be required.
  6. Full height section of the structure is required showing slopes, beams and other architectural features that may affect discharge patterns.
  7. Current water availability documentation shall accompany all submittals of new systems and TI additions to mra.
  8. Installation must be by currently licensed c16 contractors.
  9. A full set of sprinkler plans must be maintained on the job site for rough and final inspections.
  10. Underground piping installations by other than sprinkler contractor must be approved prior to approval of fire sprinkler plans.
  11. Smoke detectors are required.
  12. A minimum one (1) inch water meter is required.
All plan checks are done at the San Gabriel Fire Prevention Bureau.